CWW/Y/A 1002-T÷7202-T
A CLASS ENERGY EFFICIENCY WATERCOOLED LIQUID CHILLERS WITH (INVERTER) SCREW COMPRESSORS AND SHELL AND TUBE EXCHANGERS
The liquid Chillers of the CWW/Y/A 1002-T÷7202-T series, with A CLASS energy efficiency and R134a refrigerant, are designed to satisfy the needs of the service sector or industrial systems requiring high power.
Equipped with latest generation Screw compressors, shell and tube exchangers and connections for condensation with cooling tower water or well water or with a Dry-Cooler, these units have a series of accessories which are factory fitted or supplied separately. Designed and produced to optimize the layout of each component so as to make any necessary maintenance operations more convenient, these units have an essential and compact structure intended for indoor installation. Furthermore, accessories as the Inverter control on one Screw compressor or both is also available for getting the highest efficiency at part load and a significant reduction of starting current.
The units are compliant to the 2021 ErP Regulation.
On request, units can be supplied with R513A refrigerant.
Versies
- CWW/Y/A - Cooling only
- CWW/Y/A/SSL - Super silenced cooling only
Vermogen
- 250-2143 kW
- 71.0-609 Ton
Kenmerken
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Screw compressors with built-in oil separator, suction filter, crankcase heater, oil sight glass, thermal protection and stepless capacity steps.
- Shell and tube type condenser, with easily removable cast iron heads to enable access for maintenance operations. Each cooling circuit is supplied with an independent condenser. Water connections for cooling tower and Dry-Cooler operation; on request for well water.
- Shell and tube evaporator with two independent circuits on the refrigerant side and one on the water side, complete with water differential pressure switch.
- Cooling circuit shut-off valves on discharge and liquid line.
- Electronic expansion valve.
- Electronic high and low pressure gauges.
- R134a refrigerant. On request R513A refrigerant.
- Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors.
- Microprocessor control and regulation system.